Fabriquant français de câbles chauffants french manufacturer of heating cables french manufacturer of heating cables
Câbles
cables speciaux
Chauffage par le sol


Constant watt heating cable - PCHT

(High Temperature)

Constant watt heating cable

 

CONSTITUTING

PCHT heating cables are parallel resistance type

(to be cut to length on the job site).

The output remains constant regardless of heat transfer or surrounding temperature.

They include two bus wires individually insulated with a very high temperature silicone rubber (range 260°C).

On those bus wires, the heating wire, made of resistive alloy is spiralled.

It is energized alternately on each of the bus wires, every one meter about, so creating independent heating zones.

The insulating over sheath is made with a very high temperature silicone rubber (range 260°C).

A metallic braid can be proposed so assuming a mechanical protection and allowing to perfectly earth the installation.


WORKING PRINCIPLE

PCBT : WORKING PRINCIPLE


APPLICATIONS

Constant watt PCHT heating cables are usually designed for the following applications

· High temperature maintenance (steam or condensates pipes)

· Temperature maintenance for pipes carrying heavy fuel oil

· Temperature maintenance in pipes, tanks, up to 150°C

· Prevention against condensation


MAINS ADVANTAGES

This technology involves the following advantages :

· No thermal ageing of heating element

· No inrush current under start up conditions

· Built in cold lead

· Can be cut to length on job site

· Derivations and tee connections can be made using one single power supply (energy is available on the whole length of the cable).

· Very good flexibility

· Standard voltages : 230 or 400 volts (other voltages upon request)

· Withstand steam cleaning

· Temperature range –60°C to 260°C


MAIN CHARACTERISTICS

Circuit maximum length : 110 to 120 meters or 2500 W
Maximum temperature exposure when energized : 80 to 200°C (depending of output watts/meter)
Maximum temperature exposure when de energized : 260°C
Electrical protection (fuses) nominal power * 1.25
Differential protection : 30 mA