Fabriquant français de câbles chauffants french manufacturer of heating cables french manufacturer of heating cables
Câbles
cables speciaux
Chauffage par le sol


Constant watt heating cable - PCBT

(Low Temperature)

Constant watt heating cable

 

CONSTITUTING

PCBT heating cables are parallel resistance type (to be cut to length on the job site). The power output remains constant regardless of heat transfer or surrounding temperature.

They include two bus wires individually insulated.

On those bus wires, the heating wire, made of resistive alloy is spiralled. It is energized alternately on each of the bus wires, every one meter about, so creating independent heating zones..

WORKING PRINCIPLE

PCBT : WORKING PRINCIPLE


APPLICATIONS

PCBT/PVC constant watt heating cables are usually designed for the following applications :

- Freeze protection of water pipes, fuel

- Freeze or snow protection for gutters and roofs

- Snow elimination on access ramps and staircases

- Low temperature maintenance for pipes and tanks

MAINS ADVANTAGES

This technology involves the following advantages :

- No thermal ageing of the heating element

- No inrush current under start up conditions

- Built in cold leads

- Cut to length on the job site

- Derivations and tee connections can be made from one single power supply (energy available on the whole length of the cable)

- Very good flexibility

- Standard voltages :230 or 400 volts (other voltages upon request)

MAIN CHARACTERISTICS

Circuit maximum length : 110 to 120 meters or 1500 W
Maximum temperature exposure when energized : 40°C
Maximum temperature exposure when de energized : 105°C for PVC HT, 125°C for TPR insulation
Electrical protection (fuses) : Nominal power * 1.25
Differential protection : 30 mA

PCBT


LOAD TECHNICAL DOCUMENTATION : PDF format

SUMMARY




 
About UsContact Us
Technitrace : Avenue du général de gaulle, ZI de Toucy, 89130 TOUCY (FRANCE) * TEL : 333 86 44 06 06 * FAX : 333 86 44 09 09
Copyright © 2004, Technitrace, tous droits réservés.